Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T02EL01484
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/13/2002 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection 0000* | |
| 08/30/2002 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999*1.) PANEL FOR SPACE HAS NEUTRALS AND GROUNDS TIED INTO NEUTRAL BAR MUST BE ISOLATED, PROPERLY DEAD END LIN USED WIRING, GAS LINE CANNOT RYN 3" IN FRONT OF PANEL. SYSTEM DOES NOT HAVE GROUND. 2.) WALKIN UNIT HAS WIRING PROBLEMS EXPOSED ROMEX TO BE PROTECTED INSTALL COVER. J-BOX FOR UNIT LOOSE HAS HOLE, SO DOES LIGHT. 3.) DISCONNECT FOR ICE MACHINE LOOSE, AND CANNOT BE BEHIND UNIT. 4.) SERVICE DISCONNECT BLOCKED BY COMPRESSOR AND TABLE, SERVICE OVER FUSED AND DOUBLE LUGGED. 5.) THE ELECTRICAL SERVICE FOR THIS UNIT NEEDS TO BE ADDRESSED AND CORRECTED LABEL A# SERVICES HAVE OWNER OBTAIN SERVICES OF AN L-11 LICENSED CONTRACTOR TO MAKE CORRECTIONS WILL BE VERIFIED. |