Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/26/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR INCREASE OK CABLE DROP. |
| 07/24/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245* 1.) INSTALL BOND BUSHING WHERE USING CONCENTRIC KO'S WIHT RW'S AT BOTTOM OF PANEL 250-94 NEC. 2.) 8 X8" J-BOX TO HAVE GROUND LUG AND BONDED PER 250 NEC. |