Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/24/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*OK FINAL POWER SUBJECT TO STATE APPROVAL. |
| 07/22/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) IDENTIFY GROUNDING ELECTRODE CONDUCTOR AT GROUNDED TERMANAL 2.) INSTALL GROUNDRODS AS PER CODE. 3.) A SEALING DEVICE IS NEEDED FOR ENTRANCES ABOVE THE BUS 4.) WE ARE MISSING DEAD FRONT COVER 5.) PLEASE VERIFY LICENSED L-11 ELECTRICAL CONTRACTOR. |
| 07/18/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) PLEASE CLEAN SURFACE UNDER LUG 250-12. 2.) A SHEET METAL SCREW IS NOT ALLOWED 250-8. 3.) GROUNDING ELECTRODE CONDUCTOR TO BE CONNECTED TO GROUNDED CONDUCTOR 250-24. 4.) PLEASE PROVIDE 2ND GROUNDROD. 5.) WE HAVE MULTI POLE TERMANATION UNDER LUG. 6.) WE HAVE A LOOSE CONNECTION OF A PHASE LUG TO BOSS. MODULAR BUILDING SERVICE. |