Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/12/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) COULD NOT LOCATE PLAN/PERMIT AS PER MSG. LEFT CONTR. 2.) INSTALL BOND JUMPERS ON ALL BOND BUSHINGS. 3.) SECURE BARE GROUND TO WALL TO BLDG. |
| 08/03/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
WORKING CLEARENCE VIOLATIONS WERE EXISTING AT SERVICE, NEW ENTRANCE EQUIPMENT WAS CONNECTED TO EXISTING EQUIPMENT.2.) BONDING JUMPERS TO BE SIZED PER 250-102. 3.) WE HAVE MULTIPOLE TERMANANTIONS UNDER LUGS. 4.) PLEASE PROVIDE REJECTION PINS FOR SERVICE 5.) BOND GUTTER & DISCONNECT ENCLOSURE 6.) FINISH GAS BONDING TO ALL UNITS. |
| 07/27/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
CANCELED 7/27/02 9 AM. |