Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T02EL01454
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/24/2002 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000*OK TO CLEAR #1. OK CABLE DROP. | |
| 07/19/2002 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* 1. LABEL ON SERVICE HAS TO HAVE #1 AS ON PERMIT 2.) GFI RECEPTACLE BELOW SERVICE CONNECTED THUR OFFSET NIPPLE THRU CONCENTRIC KNOCKOUTS MUST HAVE A STRONGER SUPPORT TO BOX. 3.) 3/4 CONDUIT BELOW SERVICE TO BE STRAPPED WITH IN 3' OF PANEL. |