Permit: T02EL01442

Parcel: 133181610


Addresses:

7032 E 4TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/31/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*OK TO CLEAR/OK CABLE DROP.
07/23/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*NOTES NEED ACCESS INTO BACKYARD. GATES LOCKED. NO ANSWER AT DOOR.
07/16/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*1.) SUPPORT 1 1/2" CONDUIT WITHIN 3' OF SERVICE ENCLOSURE. 2.) SHEET METAL TEK SCREW FOR GROUND LUG IN J-BOX 10X10 UNDER PORCH NOT ALLOWED, MUST BE BOLTED, SEE ART 250 NEC. 3.) 1/2" CONDUIT MUST HAVE BUSHED CONNECTOR WHERE CABLE EXISTS ABOVE 10 X 10 J-BOX PER NEC.