Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/31/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR/OK CABLE DROP. |
| 07/23/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*NOTES NEED ACCESS INTO BACKYARD. GATES LOCKED. NO ANSWER AT DOOR. |
| 07/16/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*1.) SUPPORT 1 1/2" CONDUIT WITHIN 3' OF SERVICE ENCLOSURE. 2.) SHEET METAL TEK SCREW FOR GROUND LUG IN J-BOX 10X10 UNDER PORCH NOT ALLOWED, MUST BE BOLTED, SEE ART 250 NEC. 3.) 1/2" CONDUIT MUST HAVE BUSHED CONNECTOR WHERE CABLE EXISTS ABOVE 10 X 10 J-BOX PER NEC. |