Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/23/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/22/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) USE 20 AMP CROUSE HINDS OR MURRAY BREAKERS (2). STRAP ALL GROUND WIRE TO WALL AND TIGHTEN ALL CORRECTIONS. |
| 07/16/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) NEW DISCONNECT SWITCH NOT TO BE INSTALLED OVER 6'7" ABOVE GROUND. SEE ALSO LAST INSP. 2.) FUSES OVER SIZED IN DISCONNECT, SHOULD BE 30 AMP MAX. 6.) SUPPORT METER BASE, RISER CONDUIT, 3.) NEED ADDRESS LABEL ON DISC. SW. MUST BE PERMANENT RIVITED OR SCREWED TO ENCLOSURE 4.) GROUND CONDUCTORS CANNOT BE SPLICED BY MECHANICAL CONNECTORS OR BOLTS, MUST BE BY IRREVERSIBLE CRIMP OR X-OTHERMIC WELD. 5.) METER HIEGHT SHOULD NOT EXCEED 6' PER TEP SPECS. |
| 07/15/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245* NOTES 1.) ALL EXPOSED WIRING TO BE IN CONDUIT BELOW 8' FROM GRADE TO PROTECT FROM PHYSICAL DAMAGE. PER NEC. 2.) ALL EXPOSED WIRING ABOVE 8' MUST BE SUPPORTED AND RATED FOR SUNLIGHT EXPOSURE. 3.) INDOOR RATED MAIN DISCONNECT NEEDS TO BE REPLACED WITH OUTDOOR RATED 3R. 4.) RECALL WHEN DONE. |