Permit: T02EL01433

Parcel: 120061470


Addresses:

338 E LINCOLN ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/06/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
08/02/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999* 1.) SERVICE MUST HAVE A PERMANENT ADDRESS LABEL NO MARKER 2. STRAP GROUND WIRE TO BUILDING, IDENTIFY NEUTRAL OUT OF WEATHERHEAD WITH WHITE TAPE AT LEAST 6" OUT OF WEATHERHEAD. 3.) DRIVE GROUND RODS TO GRADE OR BELOW 4.) SERVICE TYPE (MURRAY) REQUIRES ONLY MURRAY BREAKERS NO GE OR SQUARE D. 5.) APPEARS ALL NEW WIRING HAS BEEN BROUGHT INTO NEW SERVICE A PERMIT IS REQUIRED FOR NEW WIRING PLUS IT HAS TO BE INSPECTED FIRST.