Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 08/28/2002 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999$A REINSPECTION FEE IS DUE PRIOR TO ANY INSPECTION NOTE LEFT MESSAGE IN IVR SYSTEM FOR CUSTOMER TO RETRIEVE. |
| 08/02/2002 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999*1.) MAIN SERVICE DISCONNECT CANNOT COMBINE. COPPER ALUM ON NEUTRAL LUG. 2.) CORRECT PARACELLED CONDUCTORS UNLESS OVER 3/0 COPPER. ROMEX #8 PARALLED TO BOTTOM PNL. 3.) #1 ABOVE STILL NOT DONE 4.) #3 ABOVE NOT REMOVED. |
| 07/12/2002 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999* |