Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/23/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*OK FINAL |
| 08/22/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 08/14/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000*OK TO CLEAR FOR CROSS OVER. PLEASE RECALL UPON COMPLETION WESTERN MOUNTAIN STATES IS ELECTRICAL CONTRACTOR. |
| 08/02/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
1.) IDENTIFY GROUNDING EQUIPMENT CONDUCTORS AS PER CODE. 2.) CONDUIT TO BE SEATED INTO FITTING AND TIGHTEN FITTING 4.) WE HAVE MULTIPOLE CONNECTION UNDER ACORN CLAMP AT 1ST GROUND ROD CLAMP ONLY LISTED FOR ONE. 5.) CAN NOT PASS THROUGH OLD METER SOCKET FOR USAGE. 6.) PLEASE LABEL BREAKERS. 7.) WE HAVE A WORKING CLEARENCE VIOLATION AT SUBPANEL OVER ADOBE BLOCKS 8.) PLEASE IDENTIFY NEUTRAL CONDUCTOR CLOSER TO WEATHER HEAD AND SUPPLY SUPPORTS AS PER TEP REQUIREMENTS 9.) MAIN FACTURES INSTRUCTIONS ARE NEEDED TO INSPECT TERMANATIONS AT GROUND AND NEUTRAL BAR IN SUBPANEL. 10.) PLEASE CORRECT PERMIT TO 200 AMP SERVICE UP GRADE NOT 100 AMP.11.) HAVE LICENSED ELECTRICAL CONTRACTOR PROVIED A LETTER ON COMPANY LETTER HEAD FOR RESPONSIBILTY OF WORK PER FORMED. 12.) PLEASE VERIFY BONDING TO GAS & WATER. |