Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/11/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 07/11/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*BE ADVISED, THIS PERMIT AND APPROVAL FOR CONNECTION OF THE EQUIPMENT TO THE TEP UTILITY LINES DOES NOT GRANT YOU OR THE BUILDING/BUSINESS OWNER AUTHORITY. TO RECIRCUIT, REWIRE, OR DO EXTENSIVE REWIRING WITHIN THE BUILDING. FOR THIS WORK PLACE SECURE THE PROPER PERMIT AND REQUEST THE REQUIRED INSPECTIONS. |