Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02EL01388

Parcel: 127032670


Addresses:

5620 E HAWTHORNE ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/08/2002 ELECTRIC - SERVICE UPGRADE Approved
08/01/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245* INSTALL PERMANENT ADDRESS LABEL. 2.) SUPPORT RISER CONDUIT, BOND BUSH, REQUIRE 3.) 2 GROUND RODS REQUIRED 6' MIN APART. 4.) BOND GAS PIPING.