Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date |
Description |
Inspector |
Results |
Comments |
| 08/13/2002 |
ELECTRIC - SERVICE RELOCATION |
|
Denied |
IVRS - Inspection 0210*PLEASE HAVE PERMITS FOR 1. ROOM ADDITION TO REAR OF HOUSE. 2.) GUEST HOUSE AT REAR OF PORPERTY. 3.) ENCLOSURE OF CARPORT TO LIVING SPACE. 4.) BUILDING OF BAY WINDOWS. 1. ) THE NEW ELECTRICAL METER/MAIN/LOAD CENTER IS MOUNTED ABOVE THE 6'3" MAXIMUM HEIGHT TO CENTER OF METER AS PERMITTED BY TEP. 2.) EMT CONDUIT IS NOT APPROVED FOR SERVICE RISER. |