Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/05/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 07/16/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* 1.) WE HAVE LOOSE FITTINGS @ JUNCTION BOXES. 2.) THERE ARE EXPOSED CONDUCTORS 3.) TRANSFORMER ABOVE DOOR & SIGN TO BE SECURED 4.) WE HAVE FLEXABLE CORDS ABOVE CEILING AND PASSING THROUGH CEILING TILES 5.) CORD CAPS HAVE BEEN REMOVED VIOLATION LISTING AND HARD WIRED INTO JUNCTION BOXES. 6.) WE HAVE IMPROPER MAKE UP IN JUNCTION BOX. 7.) THESE SIGNS WERE ORIGINALLY LISTED AS PORTABLE BUT HAVE BEEN INSTALLED AS PERMANENT INSTALLATION. 8.) BREAKERS ARE LABELED INCORRECTLY. 9.) CAN NOT ACCESS PANEL TO CHECK DUE WORKING CLEARANCE VIOLATION. |
| 07/15/2002 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |