Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02EL01365
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*NOTES OWNER TO OBTAIN PERMITS FOR INTERIOR OR NEXT STAGE OF CONST. INSPECTOR WILL FOLLOW UP 30 DAYS 9/5/02 | |
08/27/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*IMPROPER CLEARANCE IN FRONT OF SERVICE CATV PEDESTAL IN FRONT OF SERVICE. MUST BE AMIN OF 36". NO ACCESS TO COMPLETE INSPECTION. NEED TO SEE RODS, CONDUITS AND SUBPANEL WILL NEED A PERMIT FOR THE INTERIOR CONSTRUCTION A REINSPECTION FEE IS DUE BEFORE THE NEXT INSPECTION. | |
08/21/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*RODS HORIZONTAL MUST BE A MIN OF 30". INSTALL MAIN GROUNDING ELECTRODE CONDUCTOR AT DESIGNATED TERMINAL PER EQUIPMENT LITERATURE. NO OTHER ITEMS TO BE INFRONT OR BELOW SERVICE IE CABLE T.V. ETC. NEED GROUND BUSHING A BOND JUMPER FOR RISER. |