Permit: T02EL01363

Parcel: 133221620


Addresses:

7249 E FLAMENCO DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/31/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP.
07/30/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245* NOTES 1.) CONTR. PULLED OUT WIRING INTO HOUSE, APPEARS WORK NOT COMPLETE. 2.) A RE-FEE FOR INSPECTIONS WILL BE ASSESSED NEXT INSPECTION IF NOT READY. ALSO WILL NEED ACCESS INTO DWELLING TO CHECK WIRING CONNECTIONS.
07/24/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) PERMANENT ADDRESS LABEL REQUIRED SCREWED OR RIVITED TO ENCLOSED. PER 230-70 NEC #9287 CITY ORDIN. 2.) NEED TO VERIFY GAS PIPE BOND. 3.) I.D. CIRCUIT BREAKERS. 4.) CHASE NIPPLE NOT ALLOWE DAT CONCENTRIC KO. USE CLOSE NIPPLE WITH LOCK NUT BOTH ENDS & BOND BUSHING PER 250-94 NEC. 5.) INDIVIDUAL THWN BRNACH CIRCUIT CONDUCTORS NOT LISTED TO BE INSTALLED THRU MASONARY WALL WITHOUT RACEWAY.
07/03/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) APPREARS A RECENT SERVICE UPGRADE WAS INSTALLED AT THIS ADDRESS RECORDS AT CITY DO NOT INDICATE THIS. TEP NEVER MADE PERMANENT CONNECTION AT RISER. 2.) SUB PANEL FEEDER WAS NOT INSTALLED PER CODE. 3.) DRYER OUTLET IN UTILITY ROOM NOT PER CODE, MSUT BE FINISH WITH FINISHED WALL. 4.) OWNER TO OBTAIN PERMIT FOR SERVICE UPGRADE, 200 AMP RESIDENTAL, PLEASE ALLOW CREDIT OF RECONNECT PERMIT.