Permit: T02EL01359

Parcel: 121101500

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/19/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
07/10/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) RISER CONDUIT TO BE SUPPORTED WITH MIN 1/4" BOLTS. 2.) GROUNDING ELECTRODE CONDUCTOR FOR BOTH SERVICES TO BE CONNECTED TOGETHER WITH AN UNSPLICED BOND JUMPER. 3.) PERMANENT ADDRESS LABEL REQUIRED TO BE SCREWED OR RIVITED. 4.) INTER CONNECTION OF BRANCH CIRCUIT OR FEEDER CONDUCTORS NOT ALLOWED BETWEEN SERVICES. 5.) UNIT #2 NEEDS TO HAVE ITS OWN GROUNDING ELECTRODE SYSTEM, SEPERATE BLD.) 6.) NEED TO INSPECT FEEDER CONNECTIONS TO NEW SERVICE TO UNIT #2 WATER & GAS BOND. 7.) NEED ACCESS INTO UNIT #2. 8. HOW DID YOU RUN POWER FEEDER TO UNIT #2? 9.) NEED VERIFICATION 2ND STRUCTURE WAS PERMITTED AS A GUEST. HOUSE, NOT A GARAGE 10.) PERMIT T99CM04907 FOR CONV. FROM GARAGE TO GUEST HOUSE NEVER FINALED.