Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/19/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/10/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) RISER CONDUIT TO BE SUPPORTED WITH MIN 1/4" BOLTS. 2.) GROUNDING ELECTRODE CONDUCTOR FOR BOTH SERVICES TO BE CONNECTED TOGETHER WITH AN UNSPLICED BOND JUMPER. 3.) PERMANENT ADDRESS LABEL REQUIRED TO BE SCREWED OR RIVITED. 4.) INTER CONNECTION OF BRANCH CIRCUIT OR FEEDER CONDUCTORS NOT ALLOWED BETWEEN SERVICES. 5.) UNIT #2 NEEDS TO HAVE ITS OWN GROUNDING ELECTRODE SYSTEM, SEPERATE BLD.) 6.) NEED TO INSPECT FEEDER CONNECTIONS TO NEW SERVICE TO UNIT #2 WATER & GAS BOND. 7.) NEED ACCESS INTO UNIT #2. 8. HOW DID YOU RUN POWER FEEDER TO UNIT #2? 9.) NEED VERIFICATION 2ND STRUCTURE WAS PERMITTED AS A GUEST. HOUSE, NOT A GARAGE 10.) PERMIT T99CM04907 FOR CONV. FROM GARAGE TO GUEST HOUSE NEVER FINALED. |