Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/02/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 07/02/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0210*GROUNDING UFER MUST CONSIST OF TWO (2) GROUND RODS. THEY MUST BE SET SIX (6) FEET APART NO CLOSER. THE GROUNDING WIRE MUST BE INSTALLED UNCUT/UNSPLICED FROM ROD TO ROD TO SERVICE PANEL NEUTRAL BAR. CORRECT & RECALL LEVEL THE PEDESTAL KEEP NEAT, AND WORK MAN LIKE |