Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T02EL01302

Parcel: 124121420


Addresses:

1002 E MILES ST


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T02EL01302

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
07/10/2002 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*
07/03/2002 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*METER BASE SECTION HAS LOOSE CONNECTIONS AND MISSING SCREWS. 2.) SERVICE 60 AMP BREAKER IN OVERFUSING #10 WIRE, REPAIR COVER AND GROUND BAR HAS A LOOSE ATTACHMENT SCREWS ADDRESS SERVICES.