07/10/2002 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*
07/03/2002 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*METER BASE SECTION HAS LOOSE CONNECTIONS AND MISSING SCREWS. 2.) SERVICE 60 AMP BREAKER IN OVERFUSING #10 WIRE, REPAIR COVER AND GROUND BAR HAS A LOOSE ATTACHMENT SCREWS ADDRESS SERVICES.