Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T02EL01302
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/10/2002 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection 0000* | |
07/03/2002 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999*METER BASE SECTION HAS LOOSE CONNECTIONS AND MISSING SCREWS. 2.) SERVICE 60 AMP BREAKER IN OVERFUSING #10 WIRE, REPAIR COVER AND GROUND BAR HAS A LOOSE ATTACHMENT SCREWS ADDRESS SERVICES. |