Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/05/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR INCREASE OK CABLE DROP |
| 06/28/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*CANNOT CLAMP MULTI GROUND WIRES ON 1-ACORN CLAMP. 2.) CONNECT AN UNSPLICED GROUND ELECTRODE CONDUCTOR BETWEEN GROUND TERM BARS TO EACH SERVICES PER 250 AND 230 NEC. |