Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02EL01296

Parcel: 12511014F


Addresses:

722 N PALO VERDE BL

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/05/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*OK TO CLEAR INCREASE OK CABLE DROP
06/28/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*CANNOT CLAMP MULTI GROUND WIRES ON 1-ACORN CLAMP. 2.) CONNECT AN UNSPLICED GROUND ELECTRODE CONDUCTOR BETWEEN GROUND TERM BARS TO EACH SERVICES PER 250 AND 230 NEC.