Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02EL01288
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/26/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
07/25/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) LABEL SERVICE DISCONNECT 2. REJECT PINS ON FUSES 3.) TRANS 150 KVA MAIN BONDING JUMPER FROM UFER TO NEUTRAL REQUIRED. 4.) PLEASE MAKE PANELS PNL # PNL LDP. IN LARGER MARKING MARKING PEN OK. | |
07/24/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) DISCONNECT NEED TO BE OPENED FOR INSPECTION. NEED TO SHUT OFF TO OPEN, NO CONTRACTOR ON SITE 2.) CANNOT LOCATE A NEW SERVICE WITH LABEL #105 3.) NO PLANS ON SITE. 4.) WILL NEED ELECT CONTRACTOR TO OPEN GUTTER TO INSPECT AND INSTALL PERMANENT ADDRES LABEL. 5.) WILL NEED ELECT CONTRACTOR TO WALL THUR ON CONNECTION TO INSIDE PNL. 6.) CALL ELECT TO MEET ON SITE, REMOVER GUTTER 7.) APPEAR METER IS AFTER MAIN DISCONNECT, SHOULD THIS BE REVERSED, ALSO IS THIS A NEW LOAD OR JUST NEW METERING. |