Permit: T02EL01288

Parcel: 11520001P

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02EL01288

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/26/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
07/25/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) LABEL SERVICE DISCONNECT 2. REJECT PINS ON FUSES 3.) TRANS 150 KVA MAIN BONDING JUMPER FROM UFER TO NEUTRAL REQUIRED. 4.) PLEASE MAKE PANELS PNL # PNL LDP. IN LARGER MARKING MARKING PEN OK.
07/24/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*1.) DISCONNECT NEED TO BE OPENED FOR INSPECTION. NEED TO SHUT OFF TO OPEN, NO CONTRACTOR ON SITE 2.) CANNOT LOCATE A NEW SERVICE WITH LABEL #105 3.) NO PLANS ON SITE. 4.) WILL NEED ELECT CONTRACTOR TO OPEN GUTTER TO INSPECT AND INSTALL PERMANENT ADDRES LABEL. 5.) WILL NEED ELECT CONTRACTOR TO WALL THUR ON CONNECTION TO INSIDE PNL. 6.) CALL ELECT TO MEET ON SITE, REMOVER GUTTER 7.) APPEAR METER IS AFTER MAIN DISCONNECT, SHOULD THIS BE REVERSED, ALSO IS THIS A NEW LOAD OR JUST NEW METERING.