Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/28/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP. |
| 06/27/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*.) INSTALL PERMANENT ADDRESS LABEL ON SERVICE ENCLOSURE PER 230-70 NEC. #9287. CITY ORDIN. 2.) I.D. CIRCUIT BREAKERS. 3.) INSTALL BUSHED CONNECTOR WHERE CABLE EXITS EMT SLEEVE ABOVE 10X10 J-BOX INSTALL LOCKNUT ON 3/4" CONNECTOR AT BACK OF J-BOX, GROUND J-BOX ,CAP OFF WIRES NOT USED. 4.) INSTALL 2 GROUND RODS, MIN 6' APART PER ART 250 NEC. |