Permit: T02EL01263

Parcel: 138141810

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/27/2002 ELECTRIC - SERVICE UPGRADE Approved
06/20/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*1.) USE MIN 1/4" BOLTS TO SUPPORT RISER CONDUIT. 2.) NEED TO VERIFY GROUNDING ELECTRODE OONDUTOR IS CONTINUEOS, 3.) EXPOSE GROUND RODS FOR INSPECTION, 4.) BOND BUSHING REQUIRED WHERE USING CONCENTRIC KO'S. 5.) NEW LIGHT SWITCH, BOX, COVER, AND BOX FOR BACK PORCH LIGHT FIXTURE TO BE WEATHER PROOF.