Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/27/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
|
| 06/20/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*1.) USE MIN 1/4" BOLTS TO SUPPORT RISER CONDUIT. 2.) NEED TO VERIFY GROUNDING ELECTRODE OONDUTOR IS CONTINUEOS, 3.) EXPOSE GROUND RODS FOR INSPECTION, 4.) BOND BUSHING REQUIRED WHERE USING CONCENTRIC KO'S. 5.) NEW LIGHT SWITCH, BOX, COVER, AND BOX FOR BACK PORCH LIGHT FIXTURE TO BE WEATHER PROOF. |