Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/10/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* OK TO CLEAR INCREASE OK CABLE DROP. |
| 06/28/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.I.D. ALL CIRCUIT BREAKERS 2.) NEED TO VERIFY WATER PIPE BOND. 2.) NEED TO VERIFY WATER PIPE BOND. 3.) CHASE NIPPLE NOT APPROVED USE CLOSE NIPPLE WITH LOCKNUTS & BOND BUSHING WHERE USING CONCENTRIC KO'S 250-94 NEC. 4.) USE MIN 1/4" BOLTS TO SUPPORT RISER. |
| 06/25/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0910*PLEASE LOCK DOGS UP SO AS TO BE ABLE TO INSPECT. |