Permit: T02EL01240

Parcel: 10512024D


Addresses:

4066 N ORACLE RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/22/2009 ELECTRIC - FINAL Approved
06/25/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) DISCONNECT LABELS TO BE PERMANENT METAL LABELS 2. PLEASE PROVIDE APPROVED CITY OF TUCSON PLANS. 3.) SUPPORT CONDUITS ABOVE SHELF/ PLATFORM AS PER CODE. 4.) GROUNDING ELECTRODE CONDUCTOR TO BE CONTINOUS OR USE AN IRRVERSABLE SPLICE.
06/23/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) SUPPORT ALL CONDUITS ABOVE SHELF/PLATFORM AS PER CODE. 2.) PLEASE LABEL PANELS ON OUTSIDE COVER 3.) ALL CIRCUITS/BREAKERS NEED TO BE LABELED. 4.) CONNECTOR IN DISCONNECT IS PULLING OUT CONCENTRIES PLEASE PROVIDE LOOSE FITTINGS. 5.) TIGHTEN LOOSE FITTINGS 6.) ALL DISCONNECTS NEED TO BE LABELED 7.) PLEASE INSTALL A GROUNDING ELECTRODE SYSTEM FOR SERVICE AS PER CODE. WE ONLY HAVE A WATER BOND. 8.) PLEASE PROVIDE AN APPROVED CITY PLANS FOR INSPECTION.