Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02EL01240
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2009 | ELECTRIC - FINAL | Approved | ||
06/25/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) DISCONNECT LABELS TO BE PERMANENT METAL LABELS 2. PLEASE PROVIDE APPROVED CITY OF TUCSON PLANS. 3.) SUPPORT CONDUITS ABOVE SHELF/ PLATFORM AS PER CODE. 4.) GROUNDING ELECTRODE CONDUCTOR TO BE CONTINOUS OR USE AN IRRVERSABLE SPLICE. | |
06/23/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) SUPPORT ALL CONDUITS ABOVE SHELF/PLATFORM AS PER CODE. 2.) PLEASE LABEL PANELS ON OUTSIDE COVER 3.) ALL CIRCUITS/BREAKERS NEED TO BE LABELED. 4.) CONNECTOR IN DISCONNECT IS PULLING OUT CONCENTRIES PLEASE PROVIDE LOOSE FITTINGS. 5.) TIGHTEN LOOSE FITTINGS 6.) ALL DISCONNECTS NEED TO BE LABELED 7.) PLEASE INSTALL A GROUNDING ELECTRODE SYSTEM FOR SERVICE AS PER CODE. WE ONLY HAVE A WATER BOND. 8.) PLEASE PROVIDE AN APPROVED CITY PLANS FOR INSPECTION. |