Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/18/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*DRIVE GROUND ROD BELOW PANEL SO ITS NOT A TRIP HAZARD. 2.) PERMANENTLY MARK ADDRESS ON SERVICE NO MARKER. |
| 06/17/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0210*THE SERVICE IS NOT PER CODE SEE DIAGRAM CORRECT & RECALL. CONDUCTORS MUST BE 200A. 2/0 COPPER OR 4/0 ALUMINUM W/SUNLIGHT RESISTANT INSULATION. MINIMUM OF TWO (2) STRAPS BELOW ROOF LINE. CLAMPS ON GRD. WIRE #6 SOLID COPPER WIRE #6 SOL. COPPER GROUNDWIRE TO INCOMING BOLD. WTR. PIPE & GAS PIPE. ON HOUSE SIDE. NEW 5/8" X 8' GROUND RODS SET NOT CLOSER THAN 6' APART. TO SWG SOURCE. I.D. ALL CIRCUIT BREAKERS W/AREA SERVCED. |