Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/21/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR ECO FOR #2. PATCH THE ROOF WHERE 2" RISER GOES THUR TO KEEP WATER OFF TOP OF SERVICE. |
| 06/20/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*SEE ITEM #2-3 LAST INSP. WRITE UP. |