Permit: T02EL01197

Parcel: 121070250


Addresses:

5944 E BELLEVUE ST

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
06/18/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
06/11/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0245*1.) MUST INSTALL GROUNDING ELECT RODE SYSTEM PER ART 250,230 NEC. 2.) INSTALL PERMANENT ADDRESS LABEL PER 230-70 NEC AND #9287 CITY ORD. 3.) BOND BUSHING REQUIRED ON RISER CONDUIT PER 250-94 NEC. 4.) SEALING LOCK NUT REQUIRED ON 1" CONNECTOR ON TOP OF ENCLOSURE. 5.) LEAVE COVER OPEN 6 X 6 J-BOX TO INSPECT SPLICES.