Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 06/18/2002 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 06/11/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0245*1.) MUST INSTALL GROUNDING ELECT RODE SYSTEM PER ART 250,230 NEC. 2.) INSTALL PERMANENT ADDRESS LABEL PER 230-70 NEC AND #9287 CITY ORD. 3.) BOND BUSHING REQUIRED ON RISER CONDUIT PER 250-94 NEC. 4.) SEALING LOCK NUT REQUIRED ON 1" CONNECTOR ON TOP OF ENCLOSURE. 5.) LEAVE COVER OPEN 6 X 6 J-BOX TO INSPECT SPLICES. |