Permit: T02EL01183

Parcel: 133222480


Addresses:

500 N BAHAMAS DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/21/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
06/18/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*
06/11/2002 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection 0000*NOTES 1.) 2 GROUND RODS 5/8 X 8' LONG REQUIRED 6' MIN APART PER ART 250 NEC. 2.) BOND WATER & GAS PIPING. 250-104 NEC. 3.) INSTALL RISER, RISER CONDUCTORS, 4.) INSTALL PERMANENT ADDRESS LABEL ON ENCLOSURE.