Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T02EL01167

Parcel: 106120700

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T02EL01167

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
06/25/2002 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000* OK TO RECONNECT.
06/17/2002 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*AT THE CORD CAP THE CONDUCTORS MUST BE IN THE CAP INDIVIDUAL CONDUCTORS CANNOT BE UNDER THE CLAMP. THE CLAMP MUST BE OVER THE OUTSIDE INSULATION 2.) ROMEX WIRING INSIDE COOLER NOT REMOVED OR CORRECTED.
06/06/2002 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*1.) PLEASE REMOVE UNSAFE CORD WIRING METHODS, CORDS CAN NOT BE USED FOR PERMANENT WIRING. 2.) WE HAVE EXPOSED ROMEX CABLES. 3.) THE COVER NEED AN APPROVED WIRING METHOD. 4.) PLEASE PROVIDE A SMOKE DETECTOR. BATTERY OPERATED IS OK. 5.) CORD CAP FOR LIFE LINE IS SEPERATED AND SHOW SIGN OF MELTING.