Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T02EL01167
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2002 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection 0000* OK TO RECONNECT. | |
| 06/17/2002 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999*AT THE CORD CAP THE CONDUCTORS MUST BE IN THE CAP INDIVIDUAL CONDUCTORS CANNOT BE UNDER THE CLAMP. THE CLAMP MUST BE OVER THE OUTSIDE INSULATION 2.) ROMEX WIRING INSIDE COOLER NOT REMOVED OR CORRECTED. | |
| 06/06/2002 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999*1.) PLEASE REMOVE UNSAFE CORD WIRING METHODS, CORDS CAN NOT BE USED FOR PERMANENT WIRING. 2.) WE HAVE EXPOSED ROMEX CABLES. 3.) THE COVER NEED AN APPROVED WIRING METHOD. 4.) PLEASE PROVIDE A SMOKE DETECTOR. BATTERY OPERATED IS OK. 5.) CORD CAP FOR LIFE LINE IS SEPERATED AND SHOW SIGN OF MELTING. |