Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/25/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR BOTH UNITS #1 & #2. |
| 06/23/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*WE STILL HAVE A CIRCUIT PASSING THROUGH THE PANEL PLEASE SEPERATE CIRCUIT AND CONNECT NEUTRALS IN SAME PANEL. |
| 06/20/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 06/13/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*1.) MAINTANCE WORKING CLEARENCE IN FRONT OF PANELS LEVEL WORKING SURFACE. 2.) ACORN CLAMP ONLY LISTED FOR 1 CONDUCTOR 3.) PLEASE VERIFY GAS BONDING BOTH UNITS. 4.) WE HAVE CONDUIT OVER FILL FOR CONDUCTORS 5.) THERE ARE MULTIPOLE TERMANATION UNDER LUGS. 6.) PLEASE SEPERATE SERVICES. 7.) TIGHTEN LOOSE FITTINGS. |