Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/09/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO RECONNECT. |
| 06/13/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0935*NO VERIFICATION OF LICENSED CONTRACTOR FUSES STILL NEED TO BE RATED FOR AMPACITY A RE-FEE HAS BEEN ASSESED. |
| 05/30/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1,) FUSES TO BE RATED FOR CONDUCTOR AMPACITY. MAIN FUSES TO BE RATED FOR LOAD. 2.) PLEASE VERIFY LICENSED ELECTRICAL CONTRACTOR. LICENSED CONTRACTOR NEEDS TO PERFORM WORK. HAVE CONTRACTOR CONTACT OFFICE FOR VERIFICATION. |
| 05/28/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) WE HAVE GROUNDED RECEPTICALES ON AN UNGROUNDED SYSTEM 2. PLEASE INSTALL MISSING WALL PLATES. 3.) MAIN PULL OUT DISCONNECT FOR SUB PANEL IS MISSING. ALSO PLEASE INSTALL FUSES TO VERIFY |