Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/30/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR UPGRADE. |
| 05/24/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) USE MIN 1/4" BOLTS TO ANCHOR RISER 110-12 90-4 ALSO SEE TEP SPECS. 2.) COMPLETE WIRE TERMINATION INSIDE PANEL 3.) NEED TO VERIFY INSIDE WATER PIPING IS PVC. NO WATER BOND. |