Permit: T02EL01056

Parcel: 11014015A


Addresses:

2900 N CRAYCROFT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/09/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
12/23/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NEED PLANS
2.) LABEL NEW DISCONNECT.
11/13/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
1.) INSTALL 1/2" KO SEAL ON DISCONNECT.
2.) DOUBLE LUGGING ON EXISTING DISCONNECT LINE SIDE NOT ALLOWED. 110-3 NEC.
3.) NEUTRAL CONDUCTOR ON X-FORMER SECONDARY TO BE BONDED TO EQUIP. GROUND AND WATER LINE. 250-104A (4).
4.) USE PROPER J-BOX COVERS FOR SWITCHES ON BOILERS, EXPOSED WORK. P-RINGS AND PLASTIC PLATES NOT LISTED FOR EXPOSED INSTALLATION. 110-3 NEC.
5.) NEED CORRECT DRAWINGS REFLECTING INSTALLATION OF X-FORMER.