Permit: T02EL01052

Parcel: 138230300


Addresses:

617 W CALLE SEVILLA

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/30/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR UPGRADE.
05/23/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*MUST NOT HAVE ANYTHING FOREIGN TO THE ELECTRICAL EQUIPMENT BELOW THE SERVICE PANEL BOARD. MUST RELOCATE COX CABLE BOX TO COMPLY W/110-16 N.E.C. THE GAS LINE BELOW THIS SERVICE IS ALSO IN VIOL. OF 110-16 HOWEVER IN MY JUDGEMENT, THIS WILL ONLY SERVE A S A WARNING FOR ALL OTHER FUTURE ELECTRICAL PROJECTS.