Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/26/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*NOTIFIED CHARLES HODGES PEUBLO ELECTRIC SERVICES TO BE REMOVED FROM THIS PERMIT THEY DID NOT PERFORM WORK K TO CLEAR SERVICE INCREASE. |
| 06/24/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) HOME NOT OCCUPIED BY OWNER NEED VERIFICATION OF LICENSED CONTR. DOING WORK 2.) INSTAL PERMANENT ADDRESS LABEL ON SERVICE ENCLOSURE. PER 230-70 NEC. 9287 CITY OF TUCSON ORD. 3.) BOND GAS PIPING. 4.) INSTALL BUSHING ON 2" KO'S IN BACK OF ENCLOSURE WHERE CABLING GOES THRU. 5.) NEED TO INSP. NEW INTERIOR WIRING 6.) NEED LICENSED CONTR. TO COMPLETE ELECT. WORK & LETTER ASSUMING RESPONSIBLITY FOR THE ELECTRICAL SYSTEM INSTALLATION. 7.) SUPPORT RISER CONDUIT. TALKED TO OWNER HODGES SAID THIS HOUSE IS HAS RENTAL. |
| 06/19/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |