Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02EL01030

Parcel: 12007773B


Addresses:

4303 S 12TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/24/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
05/21/2002 ELECTRIC - SERVICE UPGRADE Denied CORRECTION REQUIRED. 1.) MARK ALL CIRCUITS OR ADD AN INDEX. 2.) THE GROUND WIRES CANNOT BE SPLICED, CONNECTED WITH KEARNEYS OR OTHER SCREW, BOLT, ETC. PRESSURE CONNECTORS. EACH WIRE MUST BE LANED ON THE NEUTRAL/GRD. BUSS OR THEY MAY BE JOINED WITH A CRIMPING DEVICE APPROVED FOR THE PURPOSE OR THEY MAY BE CAD WELDED TOGETHER. 3.) THE RISER CONDUIT MUST HAVE A MINIMUM OF TWO STRAPS FOR SUPPORT BELOW THE ROOF.