Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/24/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 05/21/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
CORRECTION REQUIRED. 1.) MARK ALL CIRCUITS OR ADD AN INDEX. 2.) THE GROUND WIRES CANNOT BE SPLICED, CONNECTED WITH KEARNEYS OR OTHER SCREW, BOLT, ETC. PRESSURE CONNECTORS. EACH WIRE MUST BE LANED ON THE NEUTRAL/GRD. BUSS OR THEY MAY BE JOINED WITH A CRIMPING DEVICE APPROVED FOR THE PURPOSE OR THEY MAY BE CAD WELDED TOGETHER. 3.) THE RISER CONDUIT MUST HAVE A MINIMUM OF TWO STRAPS FOR SUPPORT BELOW THE ROOF. |