Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/01/2002 |
ELECTRIC - FINAL |
|
Approved |
|
| 07/23/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) RISER REQUIRES 2 SUPPORTS PER TEP SPEC BOOK. 2.) SEAL PENETRATION THRU ROOF WITH ROOF CEMENT. 3.) TAKE GROUND RODS TO GRADE OR BELOW. 4.) ATTACH WATER AND GAS LINE BOND WATER LINE BY GAS. 5.) INSTALL SMALL SCREWS ON ADDRESS LABEL. 6.) USE A SPADE OR FORK CRIMP TO ATTACH STRANDED GREEN GROUND TO SCREW IN ONE GANG BOX TO RIGHT OF SERVICE. |