Permit: T02EL01017

Parcel: 11008148A


Addresses:

4610 E GLENN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/17/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR INCREASE OK CABLE DROP.
05/15/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) SUPPORT GFI RECEPTACLE BOX BELOW PANEL. 2.) USE MIN 1/4" BOLTS TO SUPPORT RISER. 3.) SERVICE DROP CONDUCTORS SHOULD HAVE MIN 8' CLEARANCE ABOVE ROOF TOP PER ART 230 NEC. SEE ALSO TEP SPEC'S.