Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T02EL01004
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/29/2002 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection 0000* | |
05/23/2002 | ELECTRIC - UNDERGROUND | Partial Approval | 1.) YOUR IN GROUND "J" BOXES MUST BE SET TO BE + - EVEN WITH THE AS PHALT SURFACE. THIS IS REQUIRED TO MINIMIZE UNEVEN SETTING AND THE POSSIBILITY OF IN ADVERTANLY CREATING A HAZARD TO AUTO TRAFFIC AND PEDESTRIANS USING THE PARKING LOTS 2.) THE ABSORBTION BED WITHIN THE BOXES MUST BE COMPLETED. 3.) ARRANGE THE WIRENUTS TO BE ELEVATED ABOVE THE BOTTOM OF THE BOX. TAPE TOGETHER IF NECESSARY. | |
05/17/2002 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*1.) U/G PVC TO POLES 13,14, 15 & 16. | |
05/16/2002 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*1.) POLES #8-10-11. 2.) CONDUIT FROM END OF TRENCH RISER, FITTINGS, AND CONNECTION TO LOAD CENTER/LIGHT CONTROL BOX OK. | |
05/15/2002 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*POLES 1,2,3,4,5,6,7,& 8, | |
05/14/2002 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*CALL FOR INSPECTION OF. OK TO COVER, |