Permit: T02EL00966

Parcel: 126171650

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/21/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*OK TO CLEAR SERVICE.
05/13/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1.) NEED A PERMANENT ADDRESS ON SERVIE 2.) NEUTRAL FOR SERVICE NEEDS TO BE TAPED WHITE INSIDE AND OUTSIDE 3.) 2" RISER TO HAVE 1 SUPPORT UNDER ROOF. PUT ROOF CEMENT AROUND PIPER ABOVE ROOF. 4.) REMOVE ALL PARTS FOR BOXES YOU WANT TO USE AS JUNCTION BOXES. 5.) ADD A GAS LINE AND WATER LINE BOND. 6.) CANNOT USE PVC PIPE ABOVE GROUND. 7.) STRAP GROUND WIRE TO STRUCTURE AND PLACE COVER OVER GROUND RODS, OR POUND TO GRADE.
05/10/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0210*