Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/21/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR SERVICE. |
| 05/13/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*1.) NEED A PERMANENT ADDRESS ON SERVIE 2.) NEUTRAL FOR SERVICE NEEDS TO BE TAPED WHITE INSIDE AND OUTSIDE 3.) 2" RISER TO HAVE 1 SUPPORT UNDER ROOF. PUT ROOF CEMENT AROUND PIPER ABOVE ROOF. 4.) REMOVE ALL PARTS FOR BOXES YOU WANT TO USE AS JUNCTION BOXES. 5.) ADD A GAS LINE AND WATER LINE BOND. 6.) CANNOT USE PVC PIPE ABOVE GROUND. 7.) STRAP GROUND WIRE TO STRUCTURE AND PLACE COVER OVER GROUND RODS, OR POUND TO GRADE. |
| 05/10/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0210* |