Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 05/15/2002 |
ELECTRIC - RECONNECT |
|
Approved |
IVRS - Inspection 0000* OK TO CLEAR. |
| 05/09/2002 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0210*CORRECTION REQUIRED 1.) THE SMOKE DETECTORS IN THE BEDROOMS MUST BE MOVED THEY MUST NOT BE CLOSER THAN 3FT. FROM THE AIR REGISTERS. 2.) THE ELECTRIC SERVICE METER AND RISED PIPE HAVE BEEN PULLED AWAY FROM THE WALL. THE ROOF SHEATHING HAS ROTTED AND WEAKENED AND THE RISER PIPE HAS BEEN PULLED THROUGH AND CLOSER TO TH END OF THE ROOF EDGE. THE WEIGHT OF THE TEP AERIAL SERVICE WIRES MUST BE SUPPORTED BY A NEW METHOD AS PRESCRIBED IN T.E.P. SERVICE MANUAL. CONTACT TEP FOR ASSISTANCE. **EXAMPLE OF SERVICE WIRING SUPPORT MAST. |