Permit: T02EL00959

Parcel: 132090870


Addresses:

2701 E NORTON VISTA

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
05/15/2002 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000* OK TO CLEAR.
05/09/2002 ELECTRIC - RECONNECT Denied IVRS - Inspection 0210*CORRECTION REQUIRED 1.) THE SMOKE DETECTORS IN THE BEDROOMS MUST BE MOVED THEY MUST NOT BE CLOSER THAN 3FT. FROM THE AIR REGISTERS. 2.) THE ELECTRIC SERVICE METER AND RISED PIPE HAVE BEEN PULLED AWAY FROM THE WALL. THE ROOF SHEATHING HAS ROTTED AND WEAKENED AND THE RISER PIPE HAS BEEN PULLED THROUGH AND CLOSER TO TH END OF THE ROOF EDGE. THE WEIGHT OF THE TEP AERIAL SERVICE WIRES MUST BE SUPPORTED BY A NEW METHOD AS PRESCRIBED IN T.E.P. SERVICE MANUAL. CONTACT TEP FOR ASSISTANCE. **EXAMPLE OF SERVICE WIRING SUPPORT MAST.