Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/16/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*OK CABLE DROP OK TO CLEAR INCREASE TEMP POWER. NOTE TO ELECTRICAN. CALL FOR FINAL APPROVAL AFTER TIE-IN OF NEW TO OLD SERVICE. |
| 05/13/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*1.) SUPPORT RISER WITHIN 3' OF ENCLOUSER PER NEC. 2.) BOND GAS PIPING PER 250-104 NEC. 3.) SERVICE DROP CONDUCTORS IN RISER TO BE SIZED ACCORDING TO TABLE 310-15(B) -6 '99NEC. 4. INSTALL PERMANENT ADDRESS LABEL. PER 230-70 NEC. #9287 CITY ORDIN. |