Permit: T02EL00954

Parcel: 110091150


Addresses:

5123 E PATRICIA ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/16/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*OK CABLE DROP OK TO CLEAR INCREASE TEMP POWER. NOTE TO ELECTRICAN. CALL FOR FINAL APPROVAL AFTER TIE-IN OF NEW TO OLD SERVICE.
05/13/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*1.) SUPPORT RISER WITHIN 3' OF ENCLOUSER PER NEC. 2.) BOND GAS PIPING PER 250-104 NEC. 3.) SERVICE DROP CONDUCTORS IN RISER TO BE SIZED ACCORDING TO TABLE 310-15(B) -6 '99NEC. 4. INSTALL PERMANENT ADDRESS LABEL. PER 230-70 NEC. #9287 CITY ORDIN.