Permit: T02EL00943

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02EL00943

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/13/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO RECONNECT.
06/10/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*PLEASE FINISH SUPPORTING CONDUIT AS NOTED. WE NEED ACCESS TO BUILDING ROOM ON ROOF. WORK IS IN PROGRESS AND LOOK A LOT BETTER THAN FIRST INSPECTION. THANK YOU.
05/08/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) JUNCTION BOX NEED TO BE PROPERLY SUPPORTED ALONG WITH CORD DROP SUPPORTS. 2.) WE HAVE EXPOSED CORD CONDUCTORS THROUGH OUT 3.) CONDUIT HAS BEEN CUT AND EXPOSING THROUGH OUT 3.) CONDUIT HAS BEEN CUT AND EXPOSING CONDUCTORS 4.) PLEASE FILL UNSED OPENINGS IN BOXES AND PANELS 5.) WE HAVE INDOOR PANEL THAT APPEARS TO HAVE WATER DAMAGE FROM A LEAKING ROOF. 6.) SUPPORT CONDUIT AS PER CODE. 7.) PLEASE INSTALL LIGHT FIXTURES AND PARTS AS PER CODE FLOURSSENTS. 8.) EXTENTION CORDS CAN NOT PASS THROUGH CIELING TILE OR BE USED FOR PERMANENT WIRING METHODS. 9.) PLEASE SUPPORT FLEX CONDUIT AS PER CODE. 10.) PLEASE PROVIDE ACCESS TO BUILDING/ROOM ON ROOF.