Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 05/08/2002 |
ELECTRIC - RECONNECT |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR RE CONN UNIT #3. |
| 05/07/2002 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0245* |
| 05/07/2002 |
ELECTRIC - RECONNECT |
|
Denied |
1.) INSTALL ADDRESS LABEL ON SERVICE DISCONNECT. 2.) INSTALL PROPER SIZE FUSES IN DISCONNECT WITH TAMPER PROFF INSERTS TO PREVENT OVERFUSING. 3.) INSTALL WEATHER PROFF COVER AND BOX FOR COOLER RECEPTACLE. 4.) REPLACE BATTERY IN SMOKE DETECTOR, AND TEST. RECALL INSP. WHEN DONE. |