Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/15/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR SERVICE DROP SUBJECT TO APPROVAL BY TEP. |
| 05/07/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0210*CORRECTION REQUIRED: 1.) THE RISER CONDUIT MUST HAVE A OF TWO TWO HOLE OR STRAPS FOR SUPPORT BELOW THE ROOF. THESE MUST BE ONE WITHIN 6" OF THE BOX AND ONE NOT CLOSER THAN 8" TO THE FIRST ONE. 2.) FLAG YOUR GROUND ROD ENDS OR EXPOSE FOR INSPECTION. 3.) LEAVE INSPECTION HISTORY CARD IN PANEL BOX AND INSTRUCTIONS ON WHERE TO FIND THE GAS PIPING BONDING CONNECTION AND THE COLD WATER PIPE BONDING CONNECTION. THANK YOU. |