Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 12/12/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 07/15/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245* 1.) INSTALL PERMANENT ADDRESS LABEL SCREWED OR RIVITED TO SERVICE ENCLOSURE 230-70 N.E.C 9287 CITY ORDIN. 2.) I.D. CIRCUIT BREAKERS. 3.) CHASE NIPPLE NOT ALLOWED AT 1 1/2 LB FOR TERM INTO PANEL. MUST HAVE CLOSE NIPPLE WITH LOCKNUTS BOTH SIDE & BOND BUSHING WHERE USING CONCENTRIC KO. 250-94 NEC. 4.) SUPPORT #4 BARE TO WALL 110-12,250 NEC. |