Permit: T02EL00878

Parcel: 123130090


Addresses:

840 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T02EL00878

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
05/08/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000* OK TO CLEAR
05/06/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0235*CORRECTIONS 1.) GROUND GAS LINE AND COLD WATER LINES. 2.) INSTALL A TWO POLE CIRCUIT BREAKERS FOR THE A/C CONDENSER UNIT. 3.) RAISE PVC CONDUIT W/UF CABLE TO BE EXPOSED. 4.) INSTALL METAL PLATE OVER OPENING ON "J" BOX.