Permit: T02EL00876

Parcel: 130070640


Addresses:

3750 E 23RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/11/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
05/02/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0210*CORRECTION REQUIRED 1.)GROUNDING REQUIRES TWO GROUND RODS. RODS MUST BE SET NOT CLOSER THAN 6FT. APART. SEE DIAGRAM BELOW 2.) THE OVERHEAD RISER CLAMPS REQUIRE LAY BOLTS 1/4" DIAMETER MINIMUM. 3.) BOND THE GAS PIPE TO THE COLD WATER PIPE. THIS MAY BE DONE AT WTR. HTR.