Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/11/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 05/02/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0210*CORRECTION REQUIRED 1.)GROUNDING REQUIRES TWO GROUND RODS. RODS MUST BE SET NOT CLOSER THAN 6FT. APART. SEE DIAGRAM BELOW 2.) THE OVERHEAD RISER CLAMPS REQUIRE LAY BOLTS 1/4" DIAMETER MINIMUM. 3.) BOND THE GAS PIPE TO THE COLD WATER PIPE. THIS MAY BE DONE AT WTR. HTR. |