Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/10/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR INCREASE OK CABLE DROP. |
| 05/01/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) BURY #4 BARE GROUNDING ELECTRODE CONDUCTOR 110-12 NEC. 2.) USE 1/4" MIN BOLTS TO SUPPORT RISER, ALSO SEE T.E.P. SPECS FOR RISER SPEC'S. 3.) GROUNDING WIRE #8 IN PANEL TO BE GREEN IN COLOR. 250-119 NEC. 4.) SCRAPE OFF PAINT UNDER GAS BOND CLAMP. 250-12 NEC. |